Business Licensing (Petroleum Storage) Regulations, 5737-1976

תקנות רישוי עסקים (אחסנת נפט), תשל"ז-1976

Published: 1976-10-19Consolidated Hebrew text as of 2024-09-18 · Last amended 2020-05-21
Premium
Unofficial English translation — for reference only. It may contain errors or omissions and cannot be relied on as a legal text. Only the Hebrew text published in Reshumot is legally binding.More

This English text was translated from the official Hebrew using a range of translation tools, and it undergoes ongoing checks and updates. It is not a certified translation.

Despite these checks, it may contain errors, omissions, or imprecise renderings of legal terminology and cross-references, and it may not yet reflect the latest amendments. It cannot be relied upon as a legal text.

The Hebrew text as published in Reshumot (ספר החוקים) and on the Knesset website is the sole authoritative and legally binding version. In any discrepancy, the Hebrew text prevails.

This translation is provided for informational purposes only and does not constitute legal advice. For use in legal proceedings, request a certified Expert Legal Opinion.

By virtue of my authority under Sections 173 and 216 of the Work Safety Ordinance [New Version], 5730-1970 (hereinafter – the Ordinance), and Section 11a of the Business Licensing Law, 5728-1968 (hereinafter – the Law), I hereby make these Regulations:

Chapter I: General

Definitions§

1.

In these Regulations –

"naked flame" – a flame, spark, electrical spark or any source having sufficient energy to cause the ignition of gases or liquids stored in an installation;

"installation owner" – any of the following:

(1)the holder of the business licence or the licence applicant, as the case may be;
(2)a person under whose supervision, control or management the business operates;
(3)the registered owner or occupier of the property in which the business is situated;

"bund" – an area on which a tank or tanks for petroleum are constructed, surrounded by walls suitable for preventing the spread of liquid beyond it;

"fence" – a built wall or strong metal mesh fence at least 2.5 metres in height with at least two gates spaced as far apart from each other as possible;

"close-mesh fence" – a fence not less than 1.8 metres in height, the lower part of which, to a height of at least 0.6 metres, is made of opaque and non-combustible material and the upper part of which is made of close mesh or opaque and non-combustible material;

"LPG" – liquefied petroleum gas;

"bund wall" – the wall surrounding the area on which a tank or tanks for petroleum are constructed, built in accordance with the requirements of these Regulations;

"licensing authority" – as defined in the Law;

"tank farm" – a site for the storage of liquid petroleum in quantities exceeding 150 cubic metres (hereinafter – cu.m.), including a terminal;

"LPG tank farm" – a site at which LPG is stored in a quantity exceeding 10 kilolitres in stationary tanks for a commercial purpose;

"dispenser" – a device used for dispensing petroleum from a storage tank, whether the pump is installed in the dispenser or within the tank;

"central supply depot" – an installation intended for the central supply of LPG at medium pressure to residential buildings, craft buildings, industry and for agricultural purposes;

"LPG warehouse" – a site at which LPG is stored for commercial purposes in tanks and cylinders to which Israeli Standard SI 70 (tanks for liquefied petroleum gases) (commercial petroleum gases) applies, as well as any depot for the central supply of LPG;

"private warehouse" – a site at which liquid petroleum is stored and used for the needs of a factory as defined in the Ordinance, in a quantity approved by the Chief Labour Inspector for the factory or for a category of factories;

"wholesale warehouse" – a site at which Class C petroleum is stored in a quantity not exceeding 50 cu.m. for the purpose of sale to retailers by tankers;

"tanker" – a motor vehicle for the transport of petroleum products;

"tank" – an LPG tank or a petroleum tank, as the case may be;

"LPG tank" – a receptacle for LPG conforming to Israeli Standard SI 158 Part 1 – Installations for Liquefied Petroleum Gases (LPG): Storage Vessels, or constructed in accordance with an accepted construction method approved by the Chief Labour Inspector;

"petroleum tank" – a receptacle for liquid petroleum conforming to one of the Israeli Standards SI 4468 Parts 1 and 2, welded steel fuel tanks, or SI 4571 Part 1, double-wall underground fuel tanks: manufacture and cathodic protection, as the case may be, or another standard approved by the Chief Labour Inspector;

"labour inspector", "regional labour inspector" and "Chief Labour Inspector" – as defined in the Organisation of Labour Inspection Law, 5714-1954;

"installation" – a tank farm, an LPG tank farm, a public filling station, an LPG warehouse, an internal filling station, a private warehouse and a wholesale warehouse;

"petroleum" – any flammable liquid or hydrocarbon gas, including LPG, natural gas and any other flammable substance declared by the Minister of Labour to be petroleum for the purposes of these Regulations, excluding lubricating greases, lubricating oils and asphalt;

"liquid petroleum" – petroleum, excluding LPG and natural gas;

"Class A petroleum" –

(1)petroleum whose flash point does not exceed 20 degrees Celsius in one of the following tests:
(a)Abel Apparatus Method HIP 170/59;
(b)Tag Closed Tester Method ASTM D 58–64;
(2)crude oil, LPG and natural gas;

"Class B petroleum" – petroleum whose flash point exceeds 20 degrees Celsius in the test referred to in the definition of Class A petroleum, but does not exceed 55 degrees Celsius in the Pensky Martens Closed Tester Method ASTM D 93–66;

"Class C petroleum" – petroleum whose flash point exceeds 55 degrees Celsius in the test referred to in the definition of "Class B petroleum";

"hazard point" – any of the following:

(1)outlet openings of pressure relief valves, ventilation and drainage valves mounted on a tank or pipe;
(2)screwed valves or flanges of any kind mounted on tanks or pipes, as well as other points at which pipes are connected or disconnected;
(3)level, volume or pressure gauges mounted on a tank or pipe;
(4)pumps, gas compressors and drainage tanks, excluding outlet openings of pressure relief valves, ventilation, level, volume and pressure gauges equipped with a 2 mm arresting nozzle, as well as pumps, gas compressors and drainage tanks forming part of a filling or discharging installation for tankers and wagons;

"tank opening" – any opening or connection to a tank through which vapours may escape into the open air, such as a ventilation pipe, a tank fuel-filling pipe and a measuring opening;

"close mesh" – mesh made of galvanised iron or non-corroding metal, in which the wire thickness is at least 0.6 mm and the size of the spaces does not exceed 12×12 mm;

"internal filling station" – a site for storing petroleum for fuelling vehicles for self-consumption in a quantity not exceeding 100 cu.m.;

"public filling station" – a site for storing petroleum for sale to the public for the purpose of fuelling vehicles or for other purposes, including an internal filling station in which the quantity of petroleum stored exceeds 100 cu.m.

Application§

2.
(a)These Regulations shall not apply to the storage of petroleum in a tank or tanks whose capacity is less than 450 litres of Class A petroleum or less than 2,200 litres of Class B or Class C petroleum, or less than 2,200 litres of Class B and C petroleum combined, provided that their total capacity does not exceed the said quantities.
(b)These Regulations shall apply to the storage of petroleum at an internal or public filling station even in a quantity less than that set out in sub-regulation (a).

Obligation to Obtain a Licence§

3.
(a)The licensing authority shall not grant a licence unless a labour inspector has approved the installation.
(b)No person shall store petroleum except at a place approved by a labour inspector.
(c)No person shall alter an installation except with the approval of a labour inspector.

Licence Application§

4.

The installation owner shall submit an application for a licence to the licensing authority in accordance with the provisions of the Business Licensing (General Provisions) Regulations, 5761-2000; the plans to be attached shall also clearly specify all particulars of the installation, including the capacity of the petroleum tanks by type, as well as details of high-voltage and extra-high-voltage power lines and electrical installations located within a distance of up to 35 metres from the installation.

5.§

(Repealed — תשס״ה)

Cleanliness of the Installation§

6.

Every installation shall be maintained in a clean condition, including free of weeds.

Storage of Objects§

7.

No person shall store or permit the storage of objects and goods in an installation except in accordance with the conditions of the licence.

Portable Receptacles§

8.

Portable receptacles containing petroleum shall not be stacked one on top of the other to a height liable to endanger their strength or the stability of the stack; LPG cylinders shall be stored upright, whether full or empty, except for cylinders without a safety valve, which shall be stored horizontally or upright.

Ventilation of Buildings§

9.

Buildings for storing portable receptacles containing petroleum shall be constructed of non-combustible material, ventilated by through-ventilation openings covered with close mesh, near the floor and near the ceiling.

Fire Prevention and Fire-Fighting Equipment§

10.
(a)No work involving a naked flame shall be carried out in an installation except with prior written approval from the person responsible for the operation of the installation and after appropriate safety measures have been taken to prevent fire.
(b)No person shall smoke in an installation except in places designated in advance by the person responsible for the operation of the installation; a visible sign shall be posted at a place so designated.
(c)Electrical equipment in an LPG tank farm and in an LPG warehouse situated in an open area within 15 metres of a hazard point shall be Explosion Proof in accordance with the provisions of SI 60079 – Electrical Equipment for Use in Explosive Gas Atmospheres: General Requirements (hereinafter – SI 60079).
(d)In the open area of an installation, within 15 metres of tanks, fittings mounted on pipes, as well as dispensers and petroleum drainage systems for Class A petroleum, electrical equipment shall be Explosion Proof in accordance with SI 60079 or Intrinsically Safe; this provision shall apply to a public or internal filling station with respect to dispensers and pumps; however, the requirement for Explosion Proof or Intrinsically Safe equipment within and around dispensers, at a public filling station and at an internal filling station, applies within a distance of 6 metres from the unit with respect to Class A petroleum and 1.5 metres with respect to Class B and C petroleum and up to the height of the space in which the pump or drive unit is located, provided that such height shall not be less than 1.5 metres.
(e)In every installation, equipment, devices and accessories shall be designated and appropriate materials shall be maintained for fire prevention and fire-fighting, as required by the fire authority; the equipment, devices, accessories and materials referred to shall be maintained in good working order and ready for use at all times; installation employees shall be instructed in the operation of the said means.

Appointment of a Responsible Person§

11.

In a tank farm and in an LPG tank farm, a person responsible for their operation shall be appointed; that person's name and address as well as the telephone number at which they can be reached shall be indicated on a sign posted in a visible place.

Entry into Tanks§

12.

No person shall enter or permit another to enter a tank except after all necessary safety measures have been taken and after obtaining written approval from the installation owner or a person authorised for that purpose.

Earthing§

13.

In a tank farm and in an LPG tank farm –

(1)the tanks and the piping system used for filling vehicles and filling other receptacles shall be earthed; the earthing shall be carried out in accordance with the specification in American Standard NFPA 77 or another suitable standard approved in advance by the Chief Labour Inspector;
(2)before filling or emptying receptacles or petroleum transport vessels, these shall be connected by means of a conductor to the tank or tanks so as to create electrical potential equalisation between them.

Distances from Power Lines§

13a.
(a)The horizontal distance from the centre of a low-voltage line of up to 1,000 volts with uninsulated wires to a tank opening and to dispensers shall be at least 5 metres.
(b)The horizontal distance from the centre of a high-voltage line of up to 33 kV with uninsulated wires to a tank opening or to a dispenser shall be at least 9 metres in an inter-urban area and at least 8 metres in an urban area.
(c)The horizontal distance between the outer wire of a high-voltage line exceeding 33 kV shall be –
(1)to the boundary of the installation – at least 10 metres;
(2)to a tank opening, to a dispenser for Class A petroleum and for LPG – at least 25 metres;
(3)to a tank opening, to a dispenser for Class B or C petroleum – at least 15 metres.
(d)In a tank farm and in an LPG tank farm, every overhead electrical power line that can release sufficient energy to ignite an explosive mixture by disconnection, short circuit or earthing shall terminate outside the tank area and outside the drainage system for Class A petroleum.

Deviations from Distances§

13b.

The Chief Inspector may prescribe deviations from the distances set out in regulation 13a and under conditions to be prescribed in each individual case, if the distance from tank openings or from a dispenser to electricity poles justifies this in his opinion; if the distance between electricity poles is less than customary, if protection exists beneath the wires preventing their contact with installations or the ground, or if the installation is in an urban area.

Shelters§

14.

A person constructing a shelter shall ensure that petroleum and petroleum vapours do not accumulate in it.

Chapter II: Tank Farms

Permitted Quantities§

15.

No person shall store or permit the storage of petroleum in a tank farm in a quantity exceeding that approved by the regional inspector or otherwise than in accordance with the conditions and restrictions he has prescribed.

Fencing§

16.

A tank farm shall be enclosed by a fence.

Prohibitions and Signage in a Tank Farm§

16a.

In a tank farm –

(1)no person shall smoke or use a mobile telephone or communication device that does not meet the requirements of regulation 10(c) and (d), except in a building situated within it;
(2)a warning sign shall be installed bearing the text "No smoking and no use of a mobile telephone or communication device that is not explosion-proof except in a building" or similar text explaining by graphic means.
17.§

(Repealed — תשס״ה)

Prohibition on Bringing in Matches and Lighters§

18.

No person shall bring matches or lighters into a tank farm except with the consent of the person responsible for its operation.

Storage of Class A Petroleum§

19.

Class A petroleum shall be stored in floating-roof tanks, or in tanks with special suitable arrangements approved in advance by the Chief Inspector.

Distances between above-ground tanks§

20.

The distance between the walls of two adjacent above-ground tanks shall be as follows:

(1)where one of them contains Class A or Class B petroleum – not less than half the sum of the diameters of the tanks, and not less than 6 metres;
(2)where both tanks contain Class C petroleum – not less than 6 metres.

Distances between tanks and fence§

21.

The distance between the wall of an above-ground tank and the fence of a tank farm shall be as follows:

(1)for a tank containing Class A or Class B petroleum – not less than 15 metres;
(2)for a tank containing Class C petroleum – not less than 6 metres.

Bund§

22.
(a)Above-ground tanks shall be installed within a bund.
(b)The capacity of a bund for tanks containing Class A or Class B petroleum shall be at least equal to the total capacity of the tanks within it.
(c)The capacity of a bund for tanks containing Class C petroleum shall be at least 110% of the capacity of the largest tank within it.
(d)A bund wall shall be –
(1)of the height required to create the capacity referred to in sub-regulations (b) and (c);
(2)impermeable to the passage of petroleum;
(3)capable of withstanding the hydrostatic pressure of a column of water at its full height on one side;
(4)constructed of earth, concrete or a material with properties similar thereto.
(e)The distance from the wall of a petroleum tank to the bund wall shall not exceed 30 metres in a bund containing one tank, and 15 metres in a bund containing more than one tank.
(f)A shared bund shall not be constructed for a number of petroleum tanks unless all of the following conditions are met:
(1)the capacity of the largest tank within it does not exceed 3,000 cu.m.;
(2)the total capacity of the petroleum tanks within it does not exceed 6,000 cu.m.;
(3)the number of Class A or Class B petroleum tanks does not exceed four.

Bund drainage§

23.
(a)Every bund shall have a drainage system fitted with valves that can be operated conveniently.
(b)The drainage of the bund shall be directed outwards and without passing through an adjacent bund.
(c)The drainage system shall discharge into a suitable oil separator that prevents petroleum from leaving the farm area.

Roads for fire-fighting vehicles§

24.

A tank farm shall be equipped along its inner fences with a road for the passage of fire-fighting vehicles, as well as other access and transit roads, which –

(1)are not less than 3.0 metres in width;
(2)are of sufficient strength for passage in all seasons of the year by a four-wheel-drive vehicle weighing at least 27 tonnes;
(3)allow a vehicle to approach the wall of a petroleum tank to within 30 metres thereof;
(4)have passing bays for parked vehicles at intervals of at least every 100 metres, as well as the ability to turn a vehicle around at the end of a dead-end road.

Deviations from distances and capacity§

25.

The Chief Inspector may approve distances smaller than those prescribed in regulations 20 and 21, and may permit a deviation from the capacity referred to in regulation 22(f) and from the provision of regulation 23(b), if, after consultation with the fire authority on all matters relating to fire prevention and fire-fighting, the circumstances justify it in his opinion.

Page 1 of 3

Read the entire law on one page — continuous text, no page breaks, plus formal citations.

RegulationsHealthLabor LawCorporate & Business

תקנות רישוי עסקים (אחסנת נפט), תשל"ז-1976

petroleum storage regulations

business licensing petroleum storage

takkanot rishuuy eskakim achsanat neft

oil storage licensing

petroleum storage licensing 1976

achsanat neft regulations

oil storage business licence

petroleum storage rules 5737

fuel storage licensing israel