Business Licensing (Petroleum Storage) Regulations, 5737-1976

תקנות רישוי עסקים (אחסנת נפט), תשל"ז-1976

Published: 1976-10-19Consolidated Hebrew text as of 2024-09-18 · Last amended 2020-05-21
Premium
Unofficial English translation — for reference only. It may contain errors or omissions and cannot be relied on as a legal text. Only the Hebrew text published in Reshumot is legally binding.More

This English text was translated from the official Hebrew using a range of translation tools, and it undergoes ongoing checks and updates. It is not a certified translation.

Despite these checks, it may contain errors, omissions, or imprecise renderings of legal terminology and cross-references, and it may not yet reflect the latest amendments. It cannot be relied upon as a legal text.

The Hebrew text as published in Reshumot (ספר החוקים) and on the Knesset website is the sole authoritative and legally binding version. In any discrepancy, the Hebrew text prevails.

This translation is provided for informational purposes only and does not constitute legal advice. For use in legal proceedings, request a certified Expert Legal Opinion.

Chapter III: LPG Tank Farms

Permitted quantities§

26.

No person shall store or permit to be stored LPG in an LPG tank farm in a quantity exceeding that approved by the Chief Inspector, or agreed to by the Minister of Defence or a person authorised by him for that purpose, or otherwise than in accordance with the conditions and restrictions prescribed by them.

Fencing§

27.

An LPG tank farm shall be enclosed by a fence.

Fire-fighting equipment§

28.

In every LPG tank farm –

(a)equipment, instruments and accessories shall be installed and suitable fire-fighting materials shall be maintained in accordance with the requirements of the fire authority; these shall be kept in proper condition and ready for use at all times;
(b)farm employees shall be trained in the operation of these means.

LPG storage§

29.
(a)LPG in an LPG farm shall be stored in fixed tanks connected by pipework to an unloading or filling system.
(b)The areas beneath above-ground LPG tanks shall be prepared in a manner that ensures, in the event of a leak, rapid drainage of liquid LPG to a site at least 10 metres from any other LPG tank; the capacity of the site for draining the liquid LPG shall be at least 50% of the capacity of the largest tank draining into it.
(c)LPG in refrigerated tanks shall be stored in accordance with the instructions of the Chief Inspector.

Distances between tanks§

30.
(a)The distance between the walls of adjacent horizontal above-ground LPG tanks shall be not less than 150 cm.
(b)The distance between the walls of adjacent spherical above-ground LPG tanks shall be not less than the diameter of the largest tank among them.
(c)The distance between the wall of a tank and the filling or unloading point of an LPG tanker or wagon, or the edge of a filling or storage surface for portable LPG cylinders, shall be not less than 10 metres.
(d)The distance between an LPG tank and tanks for the storage of Class B or Class C petroleum products shall be not less than 15 metres.

Distances between tanks and fence, building, etc.§

31.
(a)The distance between the wall of a stationary above-ground LPG tank and the fence, office, warehouse, workshop and the like shall be not less than 20 metres.
(b)The distance between a hazard point and the fence, office, warehouse, workshop and the like shall be not less than 20 metres.
(c)For the purposes of sub-regulation (b), "hazard points" are the hazard points set out below:
(1)outlet openings of pressure-relief valves, ventilation and drainage valves fitted to a tank or pipework;
(2)threaded or flanged valves of all types fitted to tanks or pipework;
(3)level, volume or pressure gauges fitted to a tank or pipework;
(4)pumps, gas compressors and drainage tanks,

excluding outlet openings of pressure-relief valves, ventilation, level, volume and pressure gauges fitted with a 2 mm restrictor nozzle, as well as points as aforesaid that form part of a tanker or wagon filling or unloading installation.

Prevention of leakage§

32.

In an LPG tank farm, effective measures shall be taken to the satisfaction of the Chief Inspector to prevent the leakage of LPG beyond the farm.

Roads for fire-fighting vehicles§

33.

An LPG tank farm shall be equipped with roads and access and transit roads as referred to in regulation 24.

Deviations from distances§

34.

The Chief Inspector may prescribe distances smaller than those prescribed in regulations 30 and 31 if in his opinion the circumstances justify it.

Chapter IV: Public Filling Stations

LPG fuelling§

34a.
(a)At a public filling station at which LPG fuelling is carried out, the requirements of Standard SI 5512, Installations for Fuelling Vehicles with Liquefied Petroleum Gas (LPG), in the updated edition (hereinafter – SI 5512), shall be complied with in respect of installations for fuelling vehicles with LPG.
(b)The provisions of regulations 35 to 47 shall not apply to installations for fuelling vehicles with LPG.

Permitted quantities§

35.

No person shall store or permit to be stored petroleum at a public filling station in a quantity exceeding that approved by the Regional Inspector or otherwise than in accordance with the conditions and restrictions prescribed by him.

Burial of tanks and their covers§

36.

Petroleum shall be stored only in underground tanks in which both of the following conditions are met:

(1)they have been covered with a layer of earth of at least 0.6 metres in thickness or have been buried as referred to in regulation 38; however, where it is not practicable to bury tanks underground, the Chief Inspector may permit the tank to be covered with a layer of earth of at least 0.6 metres in thickness whose edges shall be finished with a slope or protective walls so as to prevent the exposure of the tank due to rain and wind;
(2)the distance between two adjacent petroleum tanks and the distance between a tank and the boundary of the plot shall be not less than 0.5 metres.

Protection of underground tanks§

37.

Petroleum shall be stored only in tanks that have been buried outside vehicle traffic lanes and the area above them is protected against vehicles driving onto it by one of the following:

(1)kerb stones of at least 0.15 metres in height around the area in which the tanks are buried;
(2)protective posts made of iron pipes of a diameter not less than 3", of a height not less than 0.9 metres above ground level and at intervals not exceeding 1.5 metres from each other;
(3)a fence or railing of not less than 0.9 m in height.

Burial of a tank beneath a vehicle lane§

38.

Where it is not practicable to comply with the provisions of regulation 37, it is permitted at a public filling station to bury a tank or part thereof beneath a vehicle lane or in a place over which a vehicle may travel, or beneath the alignment of a dispenser unit or any other alignment, provided that both of the following conditions are met:

(1)above the tank there is a layer of earth of at least 0.4 metres in thickness and above it a reinforced concrete slab has been placed whose dimensions project horizontally at least 1 metre beyond the ends of the tank; the reinforced concrete shall comply with the requirements of SI 466: Code of Practice for Concrete and SI 412: Loads on Structures – Characteristic Loads, Table 12, vehicle type (3);
(2)a manhole in the concrete slab shall be covered with a cover of strength equal to that of the concrete slab.

Distances from Tank Openings to Roads and Buildings§

39.

A petroleum tank opening shall be distanced in accordance with the type of petroleum stored therein as follows:

Distances from Tank Openings to Roads and Buildings
Class A PetroleumClass B or C Petroleum
——Distances from tank openings to roads and buildings in metres
(1)From a public-authority pavement4.50.5
(2)From a public-authority pavement if there is a separation by a close-mesh fence extending at least 1 metre on each side of the opening1.50.5
(3)From an internal pavement1.50.5
(4)From the boundary of a lot that does not run along a pavement or along a public-authority road1.50.5
(5)From the boundary of a lot that does not run along a pavement or along a public-authority road if there is a separation by a close-mesh fence as detailed in paragraph (2)0.50.5
(6)From the opening of a building in which there is no naked flame1.50.5
(7)From the entrance opening of a canteen, restaurant, kitchen and any building in which a naked flame exists4.50.5
(8)From an opening as referred to in paragraph (7) if there is a separation by a close-mesh fence extending at least 1 metre on each side of the building opening passage and also 1 metre beyond the tank opening1.50.5
(9)From buildings situated on an adjoining lot4.51.5
(10)From buildings situated on an adjoining lot if there is a separation by a close-mesh fence extending at least 1 metre beyond each side of the tank opening1.50.5
(11)From an electric generator4.51.5
(12)From sewage manholes of the public sewage network4.51.5

Distances from an Underground Tank to a Building§

40.
(a)The distance from the end of an underground tank to the wall of a building in which there is no naked flame shall be at least 0.5 metres.
(b)The distance from the end of an underground tank to the external wall of a basement shall be not less than 1 metre; however, it may be reduced to 0.5 metres if one of the following conditions is met:
(1)the level of the upper surface of the tank shall be below the floor of the lowest basement;
(2)the tank shall contain Class C petroleum;
(3)the tank shall be embedded in a pool of concrete impervious to the petroleum stored in the tank.
(4)the tank is a secondary tank.

Licensing of Welding Work§

41.

No welding work shall be carried out in the area of a public filling station unless the station manager has obtained approval therefor from the regional labour inspector.

Equalisation of Electrical Potential§

42.

No person shall fill a tank, nor shall any person permit a tank to be filled with petroleum, before the electrical potential between the tank and the tanker from which the petroleum is being unloaded has been equalised.

Prohibitions at a Public Filling Station§

42a.

At a public filling station –

(1)no person shall use a mobile telephone or a communication device outside a vehicle, nor shall any person smoke;
(2)a driver is required to switch off the vehicle engine during fuelling;
(3)a person shall not fuel a vehicle unless that person has verified that the vehicle engine has been switched off;
(4)the installation owner shall install at least one warning sign in Hebrew and Arabic in the following wording: "Do not use a mobile telephone or a communication device outside a vehicle; smoking is prohibited in the station area and it is mandatory to switch off the vehicle engine during fuelling", or in similar wording containing an explanation by graphic means; the sign shall be installed in a conspicuous location and shall not be obscured, and its size shall be not less than 40 cm by 50 cm.

Ventilation of Tanks§

43.

A petroleum tank shall be equipped with a ventilation pipe in which all of the following conditions are met:

(1)its diameter is not less than 1½";
(2)its upper opening is inclined downwards and is equipped with a metal mesh whose aperture dimensions do not exceed 3×3 mm, or with a suitable flame arrester;
(3)the height of its upper opening shall be at least 3.5 metres above ground level in its surroundings and at a distance of at least 1.5 metres from windows and from openings of other buildings;
(4)it shall be installed such that within a radius of 2.5 metres from the vertical line of its upper end there shall be no entrance to a basement or to any other underground structure.

Distances from a Dispenser to Roads and Buildings§

44.
(a)The wall of a dispenser shall be distanced in accordance with the type of petroleum stored therein as set out below:
(b)For the purposes of sub-regulation (a) –

"basement" – any structure whose floor level is lower than the level of the surface surrounding the dispenser;

"opening" – any opening whose lower edge is less than 0.6 metres from the ground adjacent to it.

Distances from a Dispenser to Roads and Buildings
Class A PetroleumClass B or C Petroleum
——in metres
(1)From the opening of a Class A petroleum tank3.51
(2)From the opening of a Class B or C petroleum tank3.50.5
(3)From a public-authority pavement4.51.5
(4)From a public-authority pavement separated from the dispenser by a close-mesh fence extending at least –——
—(1)4.5 metres on each side of a Class A petroleum dispenser1–
—(2)1.5 metres on each side of a Class B or C petroleum dispenser–0.5
(5)From the boundary of an unfenced lot that does not run along a pavement or a public-authority road1.50.5
(6)From the boundary of a lot as referred to in paragraph (5) if there is a separation by a close-mesh fence extending at least 1.5 metres on each side of the dispenser0.50.5
(7)From the opening of a building in which there is no naked flame0.50.5
(8)From the opening of an office and an oil store10.5
(9)From the opening of a restaurant, canteen, toilets or from the opening of another building in which a naked flame exists4.51
(10)From an opening as referred to in paragraph (9) if there is a separation by a close-mesh fence extending at least 1.5 metres on each side of the dispenser1.50.5
(11)From the opening of a shelter or a basement4.51

Covered Car Parks§

45.
(a)No dispenser shall be installed in a covered car park except by permit from the Chief Labour Inspector and subject to conditions set by him.
(b)The Chief Labour Inspector shall not permit the installation of a dispenser in a covered car park unless there is sufficient natural ventilation for the dispersal of petroleum vapours, and in the absence of sufficient natural ventilation – adequate artificial ventilation is installed.
(c)The Chief Labour Inspector shall not permit the installation of a Class A petroleum dispenser in a place whose level is lower than the level of the access road to the dispenser.
46.§

(Repealed — תשמ״א)

Deviations from Distances§

47.

The Chief Labour Inspector may determine –

(1)distances smaller than those stated in regulations 36, 39 and 44, if in his opinion the circumstances so justify;
(2)(Repealed)

Chapter V: LPG Warehouses

48.§

(Repealed — תשס״ה)

49.§

(Repealed — תשס״ה)

50.§

(Repealed — תשס״ה)

50a.§

(Repealed — תשס״ה)

51.§

(Repealed — תשס״ה)

52.§

(Repealed — תשס״ה)

LPG Central Supply Depot§

53.

A central supply depot shall be installed in accordance with Israeli Standard SI 158 Part 1: Installations for Liquefied Petroleum Gases (LPG): Storage Vessels, Chapters A, B, D and E.

53a.§

(Repealed — תשס״ה)

53a1.§

(Repealed — תשס״ה)

53b.§

(Repealed — תשס״ה)

54.§

(Repealed — תשס״ה)

55.§

(Repealed — תשס״ה)

55a.§

(Repealed — תשס״ה)

Chapter VI: Internal Filling Stations

Fuelling with LPG§

55b.
(a)At an internal filling station at which fuelling with LPG is carried out, the requirements of Standard SI 5512 shall be fulfilled with respect to installations for fuelling vehicles with LPG.
(b)The provisions of regulations 56 to 65 shall not apply to installations for fuelling vehicles with LPG.

Permitted Quantities§

56.

No person shall store, nor shall any person permit the storage of, petroleum at an internal filling station in a quantity exceeding that approved by the regional labour inspector or otherwise than in accordance with the conditions and restrictions set by him.

Storage of Class A Petroleum§

57.

Class A petroleum shall be stored in underground tanks only.

Storage of Class B or C Petroleum§

58.

Class B or Class C petroleum shall be stored in an underground tank, or in an above-ground tank in accordance with regulation 60.

Embedding, Covering and Protection of Tanks§

59.

Underground tanks shall be installed, embedded, covered and protected in accordance with regulations 36, 37 and 38.

Storage of Class B or Class C Petroleum in an Above-Ground Tank§

60.

Storage of Class B or Class C petroleum in an above-ground tank is permitted subject to the following conditions:

(1)the tanks are installed in a bund whose capacity exceeds by at least 10% the capacity of the largest tank therein;
(2)the bund has drainage openings equipped with suitable valves operable from outside;
(3)the distance between the wall of a tank and the wall of the bund shall be at least 0.5 metres for a tank whose capacity does not exceed 30 cu.m., and at least 2 metres for a tank whose capacity exceeds 30 cu.m. or where the total capacity in the bund exceeds 150 cu.m.;
(4)the distance between the walls of two adjacent tanks shall not be less than half the sum of the diameters of the tanks, provided that it shall not be less than one metre;
(5)the distance between the wall of a tank and the boundary of the lot or the wall of a building shall be at least equal to the diameter of the tank, provided that it shall not be less than 2 metres and need not exceed 6 metres;
(6)the distance between the wall of a bund and a fence or building shall allow free movement of a fire-fighting vehicle and shall be at least 3 metres in width;
(7)the fenced area shall be at a distance of at least 3 metres from the boundary of the lot unless there exists along its length an impervious wall at a height of at least 1.8 metres.
61.§

(Repealed — תשס״ה)

Distances from a Tank Opening to Roads and Buildings§

62.

The distance from a tank opening to roads and buildings shall be in accordance with regulation 39.

Distances from a Dispenser to Roads and Buildings§

63.

The distance between a dispenser and a tank opening, a public pavement, a lot boundary, a building opening, a shelter opening or a basement opening shall be in accordance with regulation 44.

64.§

(Repealed — תשס״ה)

Deviations from Distances§

65.

The regional labour inspector may determine –

(1)distances smaller than those stated in regulations 36, 37, 39, 62 and 63 if in his opinion the circumstances so justify;
(2)deviations from the distances set in regulation 13a if the distance from a tank opening or from a dispenser to electricity poles so justifies in his opinion, or if the distance between electricity poles is smaller than customary, or if the station is in an urban area.

Prohibitions at an Internal Filling Station§

65a.

At an internal filling station –

(1)no person shall use a mobile telephone or a communication device outside a vehicle, nor shall any person smoke;
(2)a driver is required to switch off the vehicle engine during fuelling;
(3)a person shall not fuel a vehicle unless that person has verified that the vehicle engine has been switched off;
(4)the installation owner shall install at least one warning sign in Hebrew and Arabic in the following wording: "Do not use a mobile telephone or a communication device outside a vehicle; smoking is prohibited in the station area and it is mandatory to switch off the vehicle engine during fuelling", or in similar wording containing an explanation by graphic means; the sign shall be installed in a conspicuous location and shall not be obscured, and its size shall be not less than 40 cm by 50 cm.

Chapter VII: Private Warehouses

Permitted Quantities§

66.

No person shall store or permit to be stored in a private warehouse petroleum in a quantity exceeding that approved by the regional inspector or otherwise than in accordance with the conditions and restrictions that he has prescribed.

Storage of Class A Petroleum§

67.

Class A petroleum shall be stored in underground tanks that have been buried, covered and protected in accordance with the provisions of regulations 36, 37 and 38.

Storage of Class B or C Petroleum§

68.

Class B or Class C petroleum shall be stored as follows:

(1)in underground tanks that have been buried, covered and protected in accordance with regulations 36, 37 and 38;
(2)in above-ground tanks –
(a)in a quantity exceeding 500 cu.m., in accordance with regulations 20, 21, 22 and 23;
(b)in a quantity not exceeding 500 cu.m., subject to the following conditions:
(1)the tanks are installed in a bund whose capacity is at least 110% of the capacity of the largest tank in it;
(2)the bund has drainage openings fitted with adequate valves operable from outside;
(3)the distance between the wall of a tank and the wall of the bund shall be at least one metre for a tank whose capacity does not exceed 30 cu.m., and at least 2 metres if the capacity of any tank exceeds 30 cu.m. or the total capacity in the bund exceeds 150 cu.m.;
(4)the distance between the walls of two adjacent tanks shall be not less than half the sum of the diameters of the tanks, provided that it shall not be less than one metre;
(5)the distance between the wall of a tank and the boundary of the plot or the wall of a structure shall be at least equal to the diameter of the tank, provided that it shall not be less than 2 metres and need not be greater than 6 metres;
(6)the distance between the bund wall and a fence or structure shall allow free movement of a fire-fighting vehicle and shall be at least 3 metres in width;
(3)in barrels in a quantity not exceeding 10 cu.m., subject to the following conditions:
(a)full barrels shall be stored separately from empty barrels;
(b)the storage area shall be enclosed by a strong metal mesh fence at a height of at least 100 cm above the ground;
(c)the enclosed area shall be at a distance of at least 3 metres from the boundary of the plot, unless there exists along its length a solid wall at a height of at least 180 cm.
69.§

(Repealed — תשס״ה)

Deviations from Distances and Capacity§

70.

The regional inspector may approve distances and conditions different from those stated in this Chapter if in his opinion the circumstances of the case justify it.