Work Safety (Safety Devices in a Pressure Installation) Regulations, 5756-1995

תקנות הבטיחות בעבודה (התקני בטיחות במיתקן לחץ), תשנ"ו-1995

Published: 1995-12-05Consolidated Hebrew text as of 2023-09-18 · Last amended 2020-05-21
Premium
Unofficial English translation — for reference only. It may contain errors or omissions and cannot be relied on as a legal text. Only the Hebrew text published in Reshumot is legally binding.More

This English text was translated from the official Hebrew using a range of translation tools, and it undergoes ongoing checks and updates. It is not a certified translation.

Despite these checks, it may contain errors, omissions, or imprecise renderings of legal terminology and cross-references, and it may not yet reflect the latest amendments. It cannot be relied upon as a legal text.

The Hebrew text as published in Reshumot (ספר החוקים) and on the Knesset website is the sole authoritative and legally binding version. In any discrepancy, the Hebrew text prevails.

This translation is provided for informational purposes only and does not constitute legal advice. For use in legal proceedings, request a certified Expert Legal Opinion.

By virtue of my authority under Sections 107, 173 and 216 of the Work Safety Ordinance [New Version], 5730-1970 (hereinafter – the Ordinance), I hereby make these Regulations:

Chapter I: Interpretation

Definitions§

1.

In these Regulations –

"authorised boiler inspector" – as defined in the Ordinance;

"pressure gauge" – a fitting designed for measuring the pressure of steam or air in a pressure installation;

"pressure installation", "steam boiler", "steam receiver" and "air receiver" – as their meaning in the Ordinance;

"water level gauge" – a fitting enabling visual monitoring of the water level in a steam boiler;

"siphon pipe" – a pipe connecting a pressure gauge to the pressure installation;

"flow area" – the area through which steam or air passes in a safety valve upon its opening at the designed pressure;

"safety valve" – a fitting designed for the release of steam or air from a pressure installation in order to prevent the pressure therein from rising above the permitted level;

"Chief Labour Inspector" and "Regional Labour Inspector" – as their meaning in the Labour Inspection (Organisation) Law, 5714-1954.

Chapter II: Pressure Gauge for a Pressure Installation

Construction of the Pressure Gauge§

2.
(a)The pressure gauge shall be suited in its construction and in the materials of which it is made for operation with steam or air, and shall be marked in a manner that enables its identification.
(b)A steam boiler shall be fitted with a pressure gauge whose diameter is not less than 160 millimetres.
(c)In a steam boiler heated by an electric heating element, in a steam receiver and in an air receiver, a pressure gauge may have a diameter of less than 160 millimetres.

Location of the Pressure Gauge§

3.
(a)In a steam boiler the pressure gauge shall be connected to the steam space and shall be readily visible to the stoker as referred to in Section 102(a)(3) of the Ordinance.
(b)In a steam receiver and in an air receiver the pressure gauge shall be connected to the upper part of the receiver or to the supply pipe between the steam receiver and the reducing valve as referred to in Section 109(b) of the Ordinance, and shall be installed so as to be readily visible to the operator.

Measurement Range and Marking§

4.

The measurement range of the pressure gauge shall be such that the maximum working pressure point appears at approximately the midpoint of its measurement range; the permitted working pressure shall be marked on the dial of the pressure gauge in a colour that is conspicuous to the eye.

Installation of the Pressure Gauge§

5.

The connection of the pressure gauge to a steam boiler and to a steam receiver shall be by means of a siphon pipe whose internal diameter is not less than 15 millimetres; in a steam boiler heated by an electric heating element, the internal diameter of the siphon pipe shall not be less than 10 millimetres.

Means for Connecting a Test Pressure Gauge§

6.

A pressure installation shall be fitted with a means enabling the attachment of a test pressure gauge.

Chapter III: Safety Valve in a Pressure Installation

Number of Safety Valves§

7.
(a)A pressure installation shall be fitted with at least one safety valve;
(b)A steam boiler whose heating surface exceeds 60 square metres shall be fitted with at least two safety valves.

Construction of the Valve§

8.

A safety valve shall be suited in its construction and in the materials of which it is made for the maximum pressure and temperature in the pressure installation and for the type of substance in the installation, and shall be marked with an identification mark in respect of these matters.

Flow Area and Opening Pressure§

9.

The total flow area and the opening pressure of the safety valve shall be such that, upon full activation, steam or air is released from the pressure installation in a quantity sufficient to prevent the pressure in the installation from rising more than 10% above the permitted level, or less than that in accordance with the installation manufacturer's instructions.

Installation of the Valve and Shut-Off Fitting§

10.
(a)A safety valve shall be installed directly on the installation or on the supply pipe between the steam receiver and the reducing valve as referred to in Section 109(b) of the Ordinance, without a shut-off fitting between it and the installation; the location of the valve shall permit convenient and safe access to it for the purpose of its inspection and adjustment.
(b)Notwithstanding the provisions of sub-regulation (a), it is permitted, with the approval of the Chief Labour Inspector, to install a shut-off fitting between the pressure installation and the safety valve subject to the following conditions:
(1)at least 2 interlocked safety valves shall be installed on the installation, whose flow area shall be as referred to in regulation 9;
(2)the disconnection of one safety valve by means of the shut-off fitting shall cause the connection of the interlocked safety valve; the flow area of the fitting and the valves shall not, at any of the aforementioned stages, be less than that referred to in regulation 9.

Control Device§

11.

A spring-type valve shall have a device enabling manual monitoring of the operation of the valve without causing a change in the adjustment of the valve.

Lead Seal§

12.

In a steam boiler the safety valve shall be sealed with a lead seal, which shall be affixed by the valve manufacturer or by the authorised boiler inspector.

Pipe§

13.

The outlet of steam or air from the safety valve shall be directed so as not to constitute a danger to persons. In a steam boiler an exhaust pipe shall be installed on the safety valve leading to the outside of the structure; the diameter of the pipe shall not be less than the diameter of the outlet aperture of the valve in order to ensure free flow through it.

Chapter IV: Water Level Gauge in a Steam Boiler

Connection to the Boiler§

14.

The water level gauge referred to in Section 102(a)(4) of the Ordinance shall be connected to the steam boiler by means of pipes whose internal diameter is not less than 20 millimetres, except in a steam boiler heated by an electric heating element, to which it shall be connected by means of pipes whose internal diameter is not less than 10 millimetres.

Installation§

15.

The water level gauge shall be installed so as to be readily visible to the boiler stoker; the minimum permitted water level shall be visible at least 30 millimetres above the lower transparent edge of the gauge; the lower water level shall be marked with an arrow or another permanent mark.

Cocks§

16.

Three cocks shall be installed on the water level gauge: a cock connected to the steam space, a cock connected to the water space and a drain cock; the drain cock shall be connected to the drainage system of the steam boiler and shall be operable without risk.

Chapter V: General

Exemption§

17.

The Chief Labour Inspector may, in special cases, exempt from the provisions of these Regulations, in whole or in part, if he is of the opinion that in the circumstances of the matter they are not applicable.

Commencement and Application§

18.
(a)These Regulations shall commence 30 days from the date of their publication (hereinafter – the commencement date).
(b)The provisions of regulation 7(b) shall apply only to a steam boiler manufactured 6 months after the commencement date or thereafter.
RegulationsHealthLabor Law

תקנות הבטיחות בעבודה (התקני בטיחות במיתקן לחץ), תשנ"ו-1995

Work Safety Pressure Installation Regulations

Pressure Installation Safety Devices

Safety Devices Pressure Installation

Takcnot Batichuyot Avoda Pressure

Pressure Vessel Safety Regulations Israel

Work Safety Regulations 1995

Safety Devices Regulations

Pressure Equipment Safety Standards

Pressure Installation Requirements

Batichuyot Avoda Mitkan Letz