Israeli Legislation.com

Gas (Safety and Licensing) (Safety of Storage of Containers and Camping Containers in an LPG Store and in an Auxiliary Store) Order, 5752-1992

צו הגז (בטיחות ורישוי) (בטיחות ההחסנה של מכלים ומכלי מחנאות במחסן גפ"מ ובמחסן עזר), תשנ"ב-1992

Published: 1992-01-09Consolidated Hebrew text as of 2026-10-01 · Last amended 2023-11-07
Premium
Unofficial English translation — for reference only. It may contain errors or omissions and cannot be relied on as a legal text. Only the Hebrew text published in Reshumot is legally binding.More

This English text was translated from the official Hebrew using a range of translation tools, and it undergoes ongoing checks and updates. It is not a certified translation.

Despite these checks, it may contain errors, omissions, or imprecise renderings of legal terminology and cross-references, and it may not yet reflect the latest amendments. It cannot be relied upon as a legal text.

The Hebrew text as published in Reshumot (ספר החוקים) and on the Knesset website is the sole authoritative and legally binding version. In any discrepancy, the Hebrew text prevails.

This translation is provided for informational purposes only and does not constitute legal advice. For use in legal proceedings, request a certified Expert Legal Opinion.

By virtue of my authority under sections 2, 29 and 30 of the Gas (Safety and Licensing) Law, 5749-1989 (hereinafter – the Law), after consultation with the Minister of Labour and Welfare, with the consent of the Minister of Police and with the approval of the Economics Committee of the Knesset, I hereby order as follows:

Chapter I: Interpretation

Definitions§

1.

In these Regulations –

"open flame" – a flame, spark, electrical spark or any source having sufficient energy to cause the ignition of LPG;

"LPG" – liquefied petroleum gas as defined in the Law;

"the Director" – the Director of Gas Safety Affairs in the Ministry of Energy and Infrastructure;

"containers" – containers and cylinders to which Israeli Standard SI 70 – Refillable Containers for Liquefied Petroleum Gases (LPG) (hereinafter – SI 70) applies, except for camping containers;

"camping containers" – LPG with a nominal capacity of up to 12 litres, to which SI 70 and 844 applies;

"stack" – a stack of containers or camping containers;

"auxiliary store" – a site in which LPG is stored, for commercial purposes, in containers and camping containers whose total capacity does not exceed 1,000 litres (500 kg of LPG);

"LPG store" – a site in which LPG is stored for commercial purposes in containers and camping cylinders whose total capacity exceeds 1,000 litres (500 kg of LPG);

"fire authority" – as its meaning in the Fire Services Law, 5719-1959;

"holder" – the owner or lessee of an LPG store or auxiliary store;

"explosion-proof" – equipment and installations of types Div 1 Group D as its meaning in Book 70 in Chapter 500 of the Regulations of the National Fire Protection Association of the United States (hereinafter – NFPA Regulations).

Chapter II: Storage Approval

Approval of an LPG Store and an Auxiliary Store§

2.
(a)A person shall not store, nor permit another to store, LPG in a store or in an auxiliary store, and shall not operate an LPG store or an auxiliary store, unless the Director has approved the LPG store or the auxiliary store.
(b)A person applying for the approval of an LPG store or an auxiliary store shall submit an application, in 4 copies, to the Director, together with plans at a scale of 1:100 of the LPG store and the auxiliary store, and shall also submit additional particulars and documents, as required by the Director.
(c)The Director shall notify the applicant of his decision on the application within 60 days of the date of its submission; however, the Director shall not refuse to approve an LPG store or an auxiliary store unless he has first given the applicant an adequate opportunity to present his arguments before him.

Chapter III: LPG Store

Prohibited Area§

3.

A person shall not establish an LPG store nor operate it in a residential area.

Prohibited Quantity of LPG in Storage§

4.

A person shall not store, nor permit another to store, LPG in an LPG store in a quantity exceeding 25 tonnes.

Storage of Containers§

5.
(a)Containers shall be stored in open areas and in separate stacks, according to their size.
(b)Containers full of LPG shall be stored in a stack separate from empty containers, and appropriate signage shall be posted.
(c)Camping containers shall be stored in protective cages.
(d)Containers, except for empty containers, shall be stored in a vertical position in a single layer with the valve facing upwards, unless the Director has approved otherwise in respect of that installation.
(e)A label as detailed in SI 1134 Part 2 shall be affixed to each container.
(f)The provisions of sub-regulations (a) and (b) do not apply to the transportation of containers in distribution trucks and trailers.

Safety Distances§

6.
(a)The distances between one stack of containers and another, or the method of positioning trucks when necessary, shall be in accordance with the rules of the fire authority.
(b)The distance between a stack of containers and a structure in which an open flame is ordinarily used shall not be less than 7.5 metres.

Electricity§

7.
(a)Electrical installations and equipment shall not be installed in the area of an LPG store unless installed in accordance with the NFPA Regulations in force.
(b)The distance between an electrical installation that is not explosion-proof and a stack of containers shall not be less than 5 metres.

Access Routes§

8.

The access route to an LPG store shall be –

(1)of a width of not less than 4 metres;
(2)of sufficient strength in all seasons of the year for the passage of a four-wheel-drive vehicle weighing at least 12 tonnes;
(3)clear of obstacles up to a height of at least 4.2 metres.

Fire Prevention§

9.
(a)Work with an open flame or welding work shall not be carried out in the area of an LPG store except with the prior written approval of the person responsible for the store, after adequate safety measures have been taken to prevent fire.
(b)A person shall not smoke in the area of an LPG store nor bring matches or lighters into it.
(c)The area of an LPG store and its immediate vicinity shall at all times be kept clear of weeds and wild plants.
(d)Lightning conductors shall be installed in an LPG store in accordance with the requirements of Israeli Standard SI 1173 (Lightning Protection Systems for Buildings and Installations).

Fire Extinguishing Means§

10.
(a)Detection and alarm means, equipment, devices, accessories and materials suitable for extinguishing shall be installed in an LPG store in accordance with the rules of the fire authority.
(b)The equipment, devices and accessories referred to in sub-regulation (a) shall be maintained in a proper condition and fit for use at all times.
(c)Store employees shall be instructed by the holder of the store in the operation of fire extinguishing means.

Security Measures§

11.
(a)An LPG store shall be fenced, to a height of at least 2.5 metres, with a fence made of dense metal mesh or constructed with drainage openings at the base of the fence.
(b)Security lighting shall be installed along the fence of the store at a height of at least 3 metres from the ground; the lighting fixtures shall be of a type suitable for external installation and protected against water.
(c)A person shall not enter an LPG store nor permit another to enter it except through the main gate and after a security check by the security officer or a person appointed by him for that purpose.
(d)Adjacent to the entrance to the LPG store, an area shall be allocated for the handling of suspicious objects, and a security pit shall be located in its vicinity; the area shall be illuminated and clearly marked, and the access route thereto shall be clear at all times.
(e)During hours when there is no activity in the LPG store, the holder shall maintain a guard or shall activate an alarm system connected to a guard centre or to the security officer of the store and to two other employees.

Security Officer§

12.
(a)The holder of an LPG store shall appoint a security officer who shall be responsible for the security of the LPG store and for carrying out all actions necessary to prevent hostile acts, in accordance with the instructions of the Israel Police.
(b)The security officer shall be instructed by the Israel Police and shall act in accordance with its instructions.
(c)The security officer shall keep a log in which events that have occurred and actions taken shall be recorded.

Appointment of a Responsible Person§

13.

The holder of an LPG store shall appoint a person responsible for its operation; the name, address and telephone number of that person shall be indicated on a sign to be posted in a conspicuous place at the entrance to the store.

Prohibition on Other Use§

14.

An LPG store shall serve for the storage of containers only, and any activity relating to another occupation or use is prohibited therein, without obtaining a permit from the Director.

Chapter IV: Auxiliary Store

Prohibition on Storage§

15.

Only containers fitted with a valve or camping containers shall be stored in an auxiliary store.

Storage of Containers§

16.

Containers shall not be stored in an auxiliary store except in a vertical position with the valve facing upwards and secured against falling.

Storage of Camping Containers§

17.
(a)Camping containers shall not be stored in an auxiliary store except in a separate stack and with a total capacity not exceeding 450 water litres.
(b)A label as detailed in SI 1134 Part 2 shall be affixed to each container.

Provisions concerning an Auxiliary Store in a Residential Building§

18.

In an auxiliary store situated in a residential building the following provisions shall apply:

(1)the auxiliary store shall be in a separate room on the ground floor (hereinafter – the storage room), which shall serve for the storage of containers and camping containers only, and any activity relating to another occupation or use is prohibited therein;
(2)at least one wall of the storage room shall be an external wall of the building;
(3)ventilation openings shall be set in the upper part and in the lower part of the external wall; the size of each ventilation opening shall not be less than 1,200 sq cm; the total area of the ventilation openings shall be at least 25% of the wall area, or shall allow 16 air changes per hour;
(4)the walls of the storage room shall have a fire resistance of at least 3 hours;
(5)the floor of the storage room shall have a downward slope of at least 2% towards the external wall;
(6)camping containers shall be stored in a special cabinet made of metal, with latticed iron sides and a base raised above the room floor; no pipes or electrical equipment shall be installed in the cabinet.

Storage of Camping Containers in a Commercial Premises§

19.
(a)In a commercial premises situated in a building, camping containers may be stored if all of the following conditions are met:
(1)the total capacity of the camping containers does not exceed 150 water litres;
(2)the containers shall be stored in protective cages;
(3)an automatic water spray system for cooling the containers shall be installed;
(4)the protective cage shall be installed in a corner of the room;
(5)the room shall be well ventilated.
(b)Notwithstanding the provisions of sub-regulation (a), one camping container of each type may be kept outside a protective cage for display purposes.

Provisions concerning an Auxiliary Store in a Yard§

20.

In an auxiliary store that is not in a building, the following provisions shall apply:

(1)the auxiliary store shall be fenced with a fence, to a height of at least 2.5 metres, made of dense metal mesh or constructed with drainage openings at the base of the fence;
(2)security lighting shall be installed along the fence of the store at a height of at least 3 metres from the ground; the lighting fixtures shall be of a type suitable for external installation and protected against water;
(3)camping containers shall be stored in protective cages;
(4)adjacent to the entrance to the auxiliary store there shall be an open area for the handling of suspicious objects, and a security pit shall be located in its vicinity;
(5)during hours when there is no activity in the auxiliary store the gate of the store shall be locked.

Electricity§

21.
(a)Electrical installations and equipment shall not be installed in the area of an auxiliary store unless installed in accordance with the NFPA Regulations in force.
(b)The distance between a non-explosion-proof electrical installation and a container shall not be less than 5 metres.

Signage§

22.
(a)At the entrance to an auxiliary store, a sign shall be placed bearing the text "Danger – flammable gas, no smoking".
(b)In the area of an auxiliary store, a sign shall be placed in a prominent location containing instructions for conduct in the store and a prohibition on the use of open flame.

Firefighting equipment§

23.
(a)In an auxiliary store, detection and alarm devices, equipment, appliances, accessories and materials suitable for firefighting shall be installed, in accordance with the rules of the fire authority.
(b)The equipment, appliances, accessories and materials referred to in subsection (a) shall be maintained in good and serviceable condition at all times.
(c)Employees of an auxiliary store shall be trained in the operation of firefighting equipment.

Safety distances§

24.
(a)In an auxiliary store located in a courtyard, the distance between the containers and the fence shall not be less than 1.5 metres.
(b)The distance between an auxiliary store and a place where activity involving an open flame, a possible source of a spark, a public road, or a basement is carried out shall not be less than 5 metres in a store located in a building, and not less than 3.5 metres in a store located in a courtyard.
(c)Notwithstanding the provisions of subsection (b), where a wall that is fire-resistant for at least 3 hours intervenes between the auxiliary store and one of the said places, the distance between the auxiliary store and the said places may be as little as 1.5 metres.

Chapter V: Miscellaneous

Exemption§

25.

Where the Director is satisfied that in the circumstances of the matter other appropriate safety measures have been taken, he may grant an exemption from the provisions of this Order, in whole or in part.

Commencement§

26.

This Order shall come into force 60 days from the date of its publication (hereinafter – the commencement date).

Transitional provisions§

27.
(a)The owner of an auxiliary store or the holder thereof who, on the eve of the commencement of this Order, used the store as an auxiliary store, shall be entitled to continue using the store as aforesaid, provided that within six months of the commencement date the store is adapted to the requirements of the Order.
(b)The Director may extend the period referred to in subsection (a) if he is satisfied that there are special reasons justifying this.
OrderAdministrative Law

צו הגז (בטיחות ורישוי) (בטיחות ההחסנה של מכלים ומכלי מחנאות במחסן גפ"מ ובמחסן עזר), תשנ"ב-1992

Gas Safety and Licensing Order 1992

Gas Order 5752

LPG storage safety order

Gaz order

Camping containers storage safety

LPG container safety regulations

Gas storage licensing order

Gafam storage safety

Propane safety and licensing

Gas containers licensing 1992